Broiler House Ventilation During Cold Weather
Providing proper minimum ventilation rates during the cold winter months will result in an optimum environment that can maximise earning potential, according to Mississippi State University's Dr Tom Tabler (Extension Professor), Jessica Wells (Extension Instructor) and Dr Wei Zhai, Assistant Extension/Research Professor.The cold weather ventilation programme
in a broiler house is designed primarily for
moisture removal. With the arrival of cooler
weather, growers and integrators must
once again address wintertime ventilation
management.
Ventilation during cold weather is
always challenging because growers do not
want to burn any more fuel than necessary
but they do want to maintain a high level
of flock performance. For most growers,
fuel is their greatest single expense during
the year. Therefore, growers tend to reduce
ventilation rates during the winter in order
to conserve fuel and lower production
costs.
However, failure to maintain an adequate
house environment can lead to poor
air and litter quality. This can result in
reduced flock performance that is detrimental
to net returns. The goal is to have the
lowest possible fuel cost that will still allow
you to provide an environment that is best
for the birds. This is accomplished by using
a minimum ventilation rate: the quantity
of fresh, outside air that must be moved
through the broiler house to absorb and
remove moisture.
* "A much under-used item in many broiler houses today is stir fans" |
Perhaps the key principle of winter
ventilation is that warm air holds more
water than cold air. Therefore, a controlled
minimum ventilation rate uses limited
quantities of cold, dry outside air like a
sponge (as this air is heated once inside the
broiler house) to absorb moisture within the
house. Integrators generally provide their
growers with guidelines on how to manage
and control minimum ventilation rates.
However, it is impossible to control
ventilation if the house is not tight. A house
that cannot achieve a minimum of 0.13–0.15
inch (curtain-sided) or 0.20–0.22 inch (solid sidewall) of water column when static
pressure-tested will use excessive amounts
of fuel to maintain the target temperature.
And in this situation, you still cannot maintain
an optimum environment because of
air entering in places you do not want, such
as loose-fitting curtains or cracks around
footings, doors, and so forth. Sealing the
house and maintaining a tight building envelope
should be the first priority to proper
ventilation during cold weather.
Some level of air exchange is necessary
because the birds need fresh air to breathe
and propane needs oxygen to burn. For example,
for every gallon of propane burned,
850 cubic feet per hour of fresh air is consumed.
In addition, 92,000Btu of heat, 108
cubic feet of carbon dioxide and 6.8 pounds
(0.8 gallon) of water is produced for every
gallon of propane burned. It is this water
that causes many of producers' problems.
With small chicks and cold weather,
moisture production can be significant. If
you burn 300 gallons of propane the first
few days with small chicks, that is like adding
240 gallons of water to the brooding
area of the broiler house (300 gallons × 0.8
gallons water per gallon propane = 240 gallons
water). This moisture must be removed
through ventilation. Otherwise, you set
yourself up for wet litter, ammonia, respiratory
issues, foot pad problems, increased
pathogen challenge, and so forth.
One way to tighten up the house and
gain better control of the amount and location
of ventilation air that enters the house
is to have solid sidewalls. Converting from
curtain-sided to solid sidewall housing
can dramatically reduce heat loss through
conduction. For example, curtain material
has an R-value of 1. However, by switching
to solid sidewall construction and installing 3.5-inch fibreglass batt insulation in the wall, the R-value
in the wall becomes R-11. A good rule of thumb is
that when you increase the R-value of a material from
R-1 to R-2, you essentially cut the heat loss through the
material by half (Campbell et al., 2008). Going from R-1
to R-8 cuts the heat loss by 85 per cent.
A much under-used item in many broiler houses
today is stir fans. Stir fans have been around for well
over 20 years now but many houses still do not have
them, even though they can reduce fuel costs as much
as 25 percent in older houses. Even newer houses can
see fuel savings of nearly 10 per cent (Campbell et al.,
2008). Stir fans break up the temperature gradient that
forms in poultry houses. Warm air rises, so the hottest
air in the house is at ceiling level. Stir fans mix hot air
with the rest of the air. This keeps hot air gently moving
back down across the litter to promote drying, and
reduces brooder run time.
You may think having baffles in your high-ceiling
house means you cannot use stir fans in winter but that
is not the case.
Paddle fans work well in houses with baffles and
have the same benefits as the 18- to 24-inch axial fans
more commonly used in low-ceiling houses. However,
paddle fans should have forward and reverse speeds
so that airflow can be directed upward in the winter to
prevent a wind-chill effect on small chicks.
Direct the airflow of axial fans horizontally toward
the end wall or perhaps slightly uphill toward the ceiling
(not down). Growers often use stirring or mixing
fans in different ways; some growers run them continuously,
while others have them tied to the controller
and alternate their operation with the vent doors. Stir
fans should remain in use from the pre-heating period
before chick arrival until the birds are at least 14 to 18
days old.
The American Society of Agricultural Engineers
indicates a ventilation system for poultry or livestock
shelters accomplishes one or more of the following
(ASAE, 1993):
- provides desired amount of fresh air, without drafts, to all parts of the shelter
- maintains temperatures within desired limits
- maintains relative humidity within desired limits, and
- maintains ammonia levels below specified levels.
Ventilation rates are designed to balance sensible
heat (dry heat) gains and losses, as well as latent heat
(moisture) gains and losses (Porter, 1998). Sources of
sensible heat in broiler houses include bird sensible
heat (body heat), mechanical heat from lights, feeder
and fan motors, etc.; supplemental heat from brooders
and furnaces; and solar heat gain. Sensible heat losses
include heat removed by ventilation, building heat
losses through curtains, doors, walls, etc.; and sensible
heat used to evaporate water. Latent heat gain sources
include water vapour from animals (manure and respiration; water vapour from evaporation (wet litter); and
water vapour in incoming air. Ventilation removes latent
heat from the broiler house.
The question is often asked, "How long do I
minimum ventilate to control moisture in the house?”
Integrator charts and guidelines are a good starting
point. However, you should consider other factors, as
well. Watch litter conditions for signs of slicking over
in spots (especially near walls and under drinker lines),
or litter sticking to your shoes or boots. Unfortunately,
by the time you recognise there is a problem, it is
almost too far out of hand to fix it. Therefore, maintaining
the proper relative humidity (RH) inside the broiler
house may be a better option.
* "Good ventilation depends on having static pressure and vent door opening widths set correctly" |
The RH should remain between 50 per cent and
70 per cent. If the RH approaches 65 per cent, consider
increasing the minimum ventilation rate. If the RH
nears 50 per cent, slightly decreasing the minimum ventilation
rate may be in order to prevent the litter from
becoming too dusty. An inexpensive RH meter can
be purchased for around $10–20 and should be fairly
accurate for up to two years. Also, take advantage of any
occasional warm winter day. Increase the minimum
ventilation rate on warm afternoons to take advantage
of extra drying potential. However, remember to set
the time back at night to its usual setting. So, the best
answer to "How long do I minimum ventilate?" is, "As
long as it takes to do the job correctly."
Good ventilation depends on having static pressure
and vent door opening widths set correctly. The
air should enter the vent door, follow the ceiling, and
flow just past the center width of the house before falling.
This means ceiling vents should open one to two inches,
while sidewall vents should open 1.5 to 2.5 inches. Less
than this will result in inadequate air volume to carry
the air to the center of the house. This will result in cold
air falling to the floor before it has had sufficient time to
be warmed, creating damp litter and chilled chicks.
When the fans are running, the air pressure inside
a broiler house is always less than the pressure outside.
The fans move air out of the house and air rushes
in through the vent doors to replace the air being
removed. This is referred to as a 'negative pressure'
system. Static pressure is actually the difference in
pressure between inside and outside air. In most cases,
the static pressure in a 40-foot-wide house should be
between 0.08 and 0.12 when minimum ventilation fans
are running. Houses wider than 40 feet may require a
higher static pressure to achieve desired results (perhaps
0.15).
A good rule of thumb is that for each 0.01 increase
in static pressure, 2 feet of 'throw' is added to the jet
of air (0.15 = approximately 30 feet of throw). However,
the higher the static pressure, the harder the fan
must work to get air into the house. Fan flow rate decreases
as static pressure increases. Therefore, there is a
tradeoff: jet penetration length versus fan airflow rate.
Litter Amendments
Litter amendments can affect ventilation rates in
broiler houses, especially when chicks are small. Litter
amendments allow growers to ventilate for moisture,
not ammonia, greatly reducing ventilation rates. Often,
ammonia concentrations of 50ppm or higher are seen
in houses with young chicks not treated with litter
amendments, even though the integrator recommended
guideline for ammonia may be 20 to 25ppm. Ammonia
concentrations of 50ppm and higher are a serious
welfare concern and can be damaging to the eyes and
respiratory systems of young birds. Damage caused
by ammonia cannot be corrected and will result in
significant reductions in bird health and performance
throughout the flock.
However, when used correctly in proper amounts,
litter amendments inhibit ammonia production until
the product is depleted, usually when the birds are approximately
10 to 14 days old. The value of the reduced
ventilation rate alone typically ranges from $400 to
$600 for the brooding period during cold weather.
In addition, improved environmental conditions can
result in better bird health and performance (Campbell
et al., 2008). Integrators often cover or cost-share the
expense of litter amendments during cold weather to
assist growers in providing the best environment possible
for the birds.
The proper minimum ventilation programme is
critical to broiler production during cold weather.
Even though the temptation is great to reduce ventilation
to save fuel, consider how much money will be
lost to poor performance, increased mortality, and
reduced market weights. Providing proper minimum
ventilation rates during winter months will result in
an optimum environment that can maximise earning
potential.
References
ASAE. 1993. ASAE EP270.5. Design of ventilation systems
for poultry and livestock shelters. In: ASAE
Standards 1993. American Society of Agricultural
Engineers, St. Joseph, MI.
Campbell, J., J. Donald, G. Simpson and K. Macklin.
2008. Get ready for winter! The five-step program.
The Poultry Engineering, Economics & Management
Newsletter. National Poultry Technology
Center, Auburn Univ. No. 55. September.
Porter, D.O. 1998. Preparing for winter: Ventilation in
poultry and livestock shelters. West Virginia Univ.
Extension Service, Morgantown. October.
January 2013